Dungeness B - combined systems-based inspection

  • Site: Dungeness B
  • IR number: 21-062
  • Date: August 2021
  • LC numbers: 10, 23, 24, 27, 28, 34

Executive summary

Purpose of intervention

The purpose of this intervention was to conduct a system-based inspection (SBI) of EDF Energy Nuclear Generation Ltd.’s (NGL’s) Dungeness B power station specifically on the combined emergency generation, and short break supplies systems, no break systems, transformers, grid and main electrical systems that support the function of the emergency cooling water sea system (ECWS). This was undertaken as part of the planned intervention strategy for the operating facilities division of Office for Nuclear Regulation (ONR).

Interventions carried out by ONR

The inspection consisted of a safety case informed SBI of the combined emergency generation, and short break supplies systems, no break systems, transformers, grid and main electrical systems to judge the systems’ performance against their safety functions. A function of these systems is to provide the infrastructure for electricity supply to Dungeness B’s ECWS pumps under normal operations and in the event of an electrical supply interruption or a grid derived disturbance. At Dungeness B there are redundant and diverse electricity supplies to the ECWS pumps for these purposes. The redundant and diverse electricity supplies are achieved through (i) the transformers, grid and main electrical systems and (ii) in the event of an electrical supply interruption or a grid derived disturbance system through the emergency generation, short break supplies and no break systems. Through remote examination of these systems, compliance inspections were performed against the following licence conditions (LC) which are provisions of the Energy Act 2013:

  • LC 10 (Training);
  • LC 23 (Operating rules);
  • LC 24 (Operating instructions);
  • LC 27 (Safety mechanisms, devices and circuits);
  • LC 28 (Examination, inspection, maintenance, and testing); and
  • LC 34 (Leakage and escape of radioactive material and radioactive waste).

The inspection was carried out by an electrical specialist inspector with support from a nuclear associate and supported by ONR’s Dungeness B site inspector. For the purposes of this report, the term “we” refers to the judgements and opinions formed by the electrical specialist inspector and nuclear associate during this intervention.

This inspection was based on sampling the implementation of the licensee’s arrangements provided by EDF NGL against the LCs. The objective of the inspection was to determine whether the licensee’s arrangements were adequately implemented and in accordance with the systems’ safety case requirements.

The intervention was performed in line with ONR's guidance requirements (as described in our technical inspection guides) in the areas inspected.

Explanation of judgement if safety system not judged to be adequate

From this inspection, we judged that the implementation of the arrangements for the combined electrical systems that support the function of the ECWS pumps met the requirements of the safety case and was adequate.

Key findings, inspector's opinions and reasons for judgements made

We consider that EDF NGL demonstrated that they have arrangements to ensure that the combined electrical systems that support the function of the ECWS pumps are inspected, maintained and operated in accordance with the safety case. The arrangements examined complied with the licensee’s legal duties on the areas sampled during the inspection. The inspection identified a number of areas for potential improvement, and although we judged that none gave rise to significant concern, the station has agreed to take action to address them.

During the course of this inspection, we identified a minor shortfall in an instruction related to a specific action to take upon receipt of an alarm. The instruction was identified as the secondary means of instructing personnel should the primary means become unavailable. The primary means was available, clear and unambiguous. We considered the shortfall to be minor in relation to the implementation of the arrangements for LC 24. We were satisfied with the station’s response to the minor shortfall identified and satisfied with the action taken to determine the extent of condition. We raised regulatory issue 8941 to monitor the determination of the extent of condition.

The inspection of the combined electrical systems that support the function of the ECWS pumps, inspected for LCs 10, 23, 24, 27, and 28, is rated as green on the basis that relevant good practice was met and any identified deficiencies in compliance arrangements were of minor significance. No inspection rating has been assigned to LC 34 as this LC was not deemed applicable to this inspection.

Conclusion of intervention

From the evidence sampled during this inspection against LCs 10, 23, 24, 27, and 28, we consider that EDF NGL’s implementation of their arrangements for the emergency generation, and short break supplies systems, no break systems, transformers, grid and main electrical systems that support the function of the ECWS pumps met the requirements of the safety case.

There are no findings from this inspection that could significantly undermine nuclear safety.  At present, no additional regulatory action is needed over and above the planned interventions at Dungeness B Power Station as set out in the integrated intervention strategy.